Moulded Case Circuit Breakers (HKKM1-4P)
![]() Moulded Case Circuit Breakers (HKKM1-4P) |
Product Description
HKKM1L Residual moulded case circuit breaker is suitable for use in circuit of rated voltage 400V, 50Hz, and rated current up to 630A, as an electrical leakage protecting device to man. It also can be used to avoid fire caused by bad insulation of electrical aparatues and earthing faults. The breaker has various protections, protecting loads from over-load, shor-circuit, and over voltage. In the circuit, the breaker is usually used to be isolator for non-frequently switching. Being of small cubicle, high breaking capacity, short arcingdistance, having isolating function, time delay function, residual current protecting function, the breaker can not be connected to circuit up and down. The connection must be following correct diagram that is terminal 1, 3, 5 connect to power lines and terminals 2, 4, 6 connect to load.
Applied standard: IEC60947-2; GB14048.2 and standards
| Rated current of release (A) | Thermodynamic release (ambient temp+40 ° C) | Operational current of magnetic release (A) | |
| 1.05In (cold state) inoperative time (h) | 1.30In (heat state) inoperative time (h) | ||
| In ≤ 63 | ≥ 1 | < 1 | 10In ± 20% |
| 63 ≤ In _ 125 | ≥ 2 | < 2 | 10In ± 20% |
| 125 ≤ In _ 630 | ≥ 2 | < 2 | 10In ± 20% , 5In ± 20% |
| Rated current of release (A) | Thermodynamic release (ambient temp+40 ° C) | Operational current of magnetic release (A) | |||
| 1.0In (cold state) not operative time (h) | 1.20In (heat state) operative time (h) | 1.50In (heat state) operative time (h) | >2In (cole state) operative time (h) | ||
| 10 ≤ In ≤ 400 | 2 | 2 | 8min | 6S < Tp ≤ 20S | 12In ± 20% |
| Type | HKKML1-100 | HKKML1-225 | HKKML1-400 | HKKML1-630 | |||||||||||||||||||
| Rated current of shell classification Inm(A) | 100 | 225 | 400 | 630 | |||||||||||||||||||
| Rated current In(A) | 16,20,25,32, 40,50,63,80,100 | 100,125,140, 160,180,200,225 | 200,225,250, 315,350,400 | 400,500,630 | |||||||||||||||||||
| Rated operational voltage Ue(V) | 400V | ||||||||||||||||||||||
| Rated insulating voltage Ui(V) | 800V | ||||||||||||||||||||||
| Poles | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | |||||||||||||||
| Arcing distance(mm) | >100 | >100 | >100 | > 100 | |||||||||||||||||||
| Breaking capacity | M | H | M | H | M | H | M | H | |||||||||||||||
| Rated operational limited breaking capacity Lcu(KA) | AC400C | 50 | 85 | 50 | 50 | 85 | 50 | 65 | 100 | 65 | 65 | 100 | 65 | ||||||||||
| Rated operational short circuit breaking capacity lcs(KA) | AC400C | 35 | 50 | 35 | 35 | 50 | 35 | 42 | 62 | 42 | 42 | 62 | |||||||||||
| Rated residual active current In(mA) | I | 100/300/500 | |||||||||||||||||||||
| I I | 30/100/300 | 300/500/1000 | |||||||||||||||||||||
| Rated residual not-active current I no(mA) | 1/2I _ no | ||||||||||||||||||||||
| Rated residual short circuit making (breaking) capacity Im(mA) | 1/4Icu | ||||||||||||||||||||||
| Operations(OPS) | Elec. | 3000 | 3000 | 2000 | 1500 | ||||||||||||||||||
| Mech. | 7000 | 7000 | 4000 | 3000 | |||||||||||||||||||
| Model NO.: | HKKM1-4P |
| Company: | Zhejiang Dahua Switch Factory |
Most Popular
-

Residual Current Circuit Breaker(F360) TECHNICAL DATA Standard: IEC1008, GB16916, BS ... -

Permanent Magnetic High Voltage Indoor Vacuum Circuit ... Major Technical Data Rated voltage: ... -

Mcb (SA1-G3 Hydraulic Magnetic) MCB Hydraulic magnetic mini circuit breaker is ...
-

Fuse Holder Hrc fuse and fuse hodler conforms to iec269-1 ... -

RCCB, Residual Current Circuit Breaker KNL1-63(F360 Series) KNL1 series Residual current circuit ... -

Residual Current Circuit Breaker CXL3 (F360) CXL3 series residual current action circuit ...
-

AP7 Mini Circuit Breaker The products have protective function as shortage ... -

Mini Circuit Breaker The design on the base of the current-limiting ... -

Motor Protection Circuit Breaker (GV2-M) GV series motor protection circuit breaker are ...
-

MCB (UKB7) Prouduct Description: Number of Poles: 1P, 2P, ... -

Mould Case Circuit Breaker SGVL(SIMENIS MODEL) 125---400AMP (3, 4POLE) -

Circuit Breaker (EE-30A) Voltage: 240V 50Hz Amp. 30A
-

Thermal Protector (ABR20-H) We are professional Circuit Breaker, overload ... -

ANL Auto Fuse Auto fuse, Mini auto fuse, Max auto fuse, ATC ... -

15KV Fuse Cutout 15KV Fuse Cutout Type: SGF-1 ...
Quick Products |
Inquiry Basket (